Specifications
Functional Characteristics
- Frequency: 50/60 Hz
- TC- Overcurrent Trip Class(777 Plus Series units): 02-60, J02-J60, L00-L60 or Off
- TC- Overcurrent Trip Class (77C, 777 non-Plus Series units): 5, 10, 15, 20, 30 (J prefix enables jam protection feature)
Output Characteristics
- Pilot duty rating: 480 VA @ 240 V ac, B300
- General purpose: 10 A @ 240 V ac
- Pilot duty rating for HVR models: 470 VA @ 600 V ac, B600
General Characteristics
- Operating: -20 °C to 70 °C (-4 °F to 158 °F)
- Storage: -40 °C to 80 °C (-40 °F to 176 °F)
Accuracy
- Voltage: ±1 %
- Current: ±3 % (<100 amps direct)
- GF Current: ±15 %
- Timing (777 Plus Series units): ±0.5 second
- Timing (77C, 777 non-Plus Series units): 5 % +1 second
Repeatability
- Voltage: ±0.5 % of nominal voltage
- Current: ±1 % (<100 amps direct)
- Maximum Input Power: 10 W
- Pollution Degree: 3
- Class of Protection: IP20
- Relative Humidity: 10–95 %, non-condensing per IEC 68-2-3
- Terminal Torque: 7 in.-lbs.
Standard Passed
- Electrostatic Discharge (ESD): IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air
- Radio Frequency Immunity (RFI), Conducted: IEC 61000-4-6, Level 3, 10 V/m
- Radio Frequency Immunity (RFI), Radiated: IEC 61000-4-3, Level 3, 10 V/m
- Fast Transient Burst: IEC 61000-4-4, Level 3, 3.5 kV input power
- Short Circuit: 100 kA
Surge
- IEC: 61000-4-5, Level 3, 2 kV line-to-line; Level 4, 4 kV line-to-ground
- ANSI/IEEE: C62.41 Surge and Ring Wave Compliance to a level of 6 kV line-to-line
- Hi-potential Test: Meets UL508 (2 x rated V +1000 V for 1 minute)
- Vibration: IEC 68-2-6, 10–55 Hz, 1 mm peak-to-peak, 2 hours, 3 axis
- Shock: IEC 68-2-27, 30g, 3 axis, 11 ms duration, half-sine pulse
- Maximum Conductor Size (with insulation) through 777/77C: 0.65”
- Dimensions: H 77.47 mm (3.05”); W 97.79 mm (3.85”); D 128.27 mm (5.05”)
- Weight: 1.56 lbs. (24.96 oz., 707.6 g)
- Mounting Method: Surface mount (4 - #8 screws) or DIN-rail mount
Ordering Information
MODEL | LINE VOLTAGE | MOTOR FULL AMP RANGE MOTOR | DESCRIPTION |
777-P2 | 200-480 V ac | 2–800 A (external CTs required above 90 A) | Provides low and high power trip*, linear overcurrent trip, and 480 VA @ 240 V ac output SPDT relay contacts. |
777-FT | 200–480 V ac | 2–800 A (external CTs required above 90 A) | Provides linear overcurrent trip and 480 VA @ 240 V ac output SPDT relay contacts. |
Accessories
S485MS-2W Communication Module
(for limited Modbus capabilities) Required to enable the Modbus communications function on Model 77X-type products.
CIO-MB/CIO-120-MB Communication Module
Modbus-RTU interfaces capable of providing discrete control and monitoring of an overload relay over a Modbus network.
CIO-DN-P/CIO-120-DN-P Communication Module
DeviceNet* interfaces capable of providing discrete control and monitoring of motor starters, drives and other devices over a DeviceNet* network.
CIO-777-PR Communication Module
Profibus interface capable of providing discrete control and monitoring of motor starters, drives and other devices over a Profibus network.
CIO-EN (non-POE) Communication Module
Modbus-TCP and Modbus-RTU interface capable of providing discrete control and monitoring of an overload relay over a Modbus network.
Communication Adapters
- RS485-RS232–Converter with cable & plug
- RS485-USB–Converter with cable & plug
- RS232-USB–Converter
Specifications match industry standard.
RM1000 Remote Monitor
The RM1000/777 motor management system combines unsurpassed electronic motor protection and critical, user-friendly, motor monitoring for up to 16 devices.
RM2000 Remote Monitor
The RM2000/777 motor management system combines unsurpassed electronic motor protection and critical, user-friendly, motor monitoring with event storage and real-time clock for date and time stamp.
Solutions Software: Solutions-M
Software features include data logging, real-time data monitoring and fault and event monitoring.
777-MRSW Manual Remote Reset Kit
Allows the 777 line of MotorSaver® and PumpSaver® products to be manually reset without opening the panel door.
OL-Reset Manual Remote Reset Kit